| Plan Review Notes For Permit 00091238 |
| Permit Number |
00091238 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* UNSAT ****************** | | | | | | | | | 1)NOTE: PLEASE NOTE; PER FL STATE STATUE | | | 'S. PLANS ARE TO SIGNED AND SEALED BY | | | ENGINEER OF RECORD ON TITLE BLOCK. | | | 61G15-23.002/CHAPTER 471 OF FL AD. CODE | | | | | | 2)NOTE: PLEASE SHOW CLARIFICATION ON | | | RISER DIAGRAM,,,METERCAN AND ??? AND | | | PANEL SHOWN?? NO WIRE SIZES,CONDUITS ETC | | | IS THIS ALL EXISTING?? IF SO PLEASE NOTE | | | AND STILL SHOW. | | | | | | 3)NOTE: PLEASE COMPLETE AND (SHOW) LOAD | | | CALCULATIONS. PLEASE NOTE THAT ALL | | | CONTINUOUS LOADS ARE TO BE SHOWN AT 125% | | | LIGHTING ETC. 215-5 | | | | | | GROUNDING SYSTEM?? PER 250 AND 215-5 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|