| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH FIRE SPRINKLER PLANS. | | | 2) A FOLDED SET OF E2.1 PLANS HAS BEEN | | | AMENDED BUT ARE NOT SIGNED AND SEALED | | | LIKE THE PLANS. THE E2.1 PLANS DO NOT | | | CORRELATE. ORIGINAL E2.1 MUST BE | | | REVISED. PLEASE REFER TO FS 61G15-23.002 | | | 471.025 | | | 3) NO INTERIOR FINISH INFORMATION | | | PROVIDED. |
|