| Plan Review Notes For Permit 00091222 |
| Permit Number |
00091222 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE SPRINKLER DRAWINGS AND HYDRAULIC | | | CALCULATIONS ARE TO BE PROVIDED WITH | | | PLANS. ACCORDING TO THE PLANS THE FIRE | | | SPRINKLERS WILL BE PERMITTED SEPARATELY | | | NO BUILDING PERMIT WILL BE ISSUED | | | WITHOUT SPRINKLER DRAWINGS. | | | 2) DOORS 01 AND 12 ARE TO BE EQUIPPED | | | WITH SELF-CLOSING DEVICES. WHEN CLOSED | | | THESE DOORS ARE REQUIRED TO POSITIVELY | | | LATCH | | | 3) PLEASE INDICATE INTERIOR FINISHES | | | FOR EXITS AND OFFICES. THE CURRENT FIRE | | | CODE REQUIRES THAT INTERIOR FINISHES | | | IN EXITS BE CLASS A OR B. INTERIOR | | | FINISHES IN OFFICES CAN BE CLASS A,B, | | | OR C. | | | 4) THE FIRE ALARM NOTES SECTION OF THE | | | PLAN INDICATES CLASS B, STYLE C | | | CIRCUITS. ONLY CLASS A, STYLE D FIRE | | | ALARM CIRCUITS ARE PERMITTED. | | | 5) PLEASE SUBMIT FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR NEW FIRE ALARM | | | EQUIPMENT SHOWN ON PLANS. CUT SHEETS | | | ARE TO BE PROVIDED WITH FIRE ALARM | | | PLANS. |
|