| Plan Review Notes For Permit 00091204 |
| Permit Number |
00091204 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** PROVISO **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS AND PANELS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. PER 110-9. | | | THIS IS REQ`D ON PLANS PER 215-5 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|