Plan Review Notes
Plan Review Notes For Permit 00091158
Permit Number 00091158
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************PROVISO*****************
 SUBMIT DETAIL OF CONNECTION OF 8"PVC TO
 INTERCEPTOR TO ENSURE WASTE WILL BE
 PROPERLY SEPARATED AND INTERCEPTOR
 EFFICIENCY WILL BE RETAINED.SPC 1004.1
  
 2)SHT.C-2-PVC CANNOT BE USED FOR WATER
 DISTRIBUTION PER SPC 611.2,611.3.
  
 3)INDICATE ON PLAN WHERE WASTE FROM EYE-
 WASH WILL DISCHARGE.DISCHARGE SHALL NOT
 CREATE A NUISANCE OR HAZARD.SPC SEC.301.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.