| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | SUBMIT DETAIL OF CONNECTION OF 8"PVC TO | | | INTERCEPTOR TO ENSURE WASTE WILL BE | | | PROPERLY SEPARATED AND INTERCEPTOR | | | EFFICIENCY WILL BE RETAINED.SPC 1004.1 | | | | | | 2)SHT.C-2-PVC CANNOT BE USED FOR WATER | | | DISTRIBUTION PER SPC 611.2,611.3. | | | | | | 3)INDICATE ON PLAN WHERE WASTE FROM EYE- | | | WASH WILL DISCHARGE.DISCHARGE SHALL NOT | | | CREATE A NUISANCE OR HAZARD.SPC SEC.301. | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|