| Plan Review Notes For Permit 00091144 |
| Permit Number |
00091144 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: ELECTRICAL HEAT PUMP NOT ON WIR- | | | -ING DIAGRAM. | | | | | | 2)NOTE: ALSO ,SUBMIT LOAD CALCUALATIONS | | | TO INCLUDE NEW HEAT PUMP. SHOW EXISTING | | | SERVICE SIZE. | | | | | | PLEASE SUBMIT LOAD CALCULATIONS AND | | | SERVICE SIZE EACH TIME PLANS ARE SUBMITT | | | -ED WITH HEAT PUMP BEING INSTALLED. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|