Plan Review Notes
Plan Review Notes For Permit 00091125
Permit Number 00091125
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
  
 2)FIXTURE BRANCHES NOT PERMITTED ON WET
 VENT PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.(RISER FOR 2ND.FLR.BATH TO
 CONNECT TO HORIZONTAL DRAIN DOWN-
 STREAM OF EXISTING WATER CLOSET.)
  
 3)A MAX.OF 2 WATER CLOSETS ARE PERMITTED
 ON A 3" BUILDING DRAIN.SPC TABLE 714.1,
 FOOTNOTE #3
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.