Plan Review Notes
Plan Review Notes For Permit 00091125
Permit Number 00091125
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SHOW CLARIFICATION OF NEW
 PANEL BEING INSTALLED. YOU SHOW MLO AND
 60A ? IS THIS GOING TO HAVE A 60 AMP
 BRKER FOR THE MAIN? IF NOT THEN A MAIN
 IS REQ`D AT DETACHED STRUCTURE.
  
 2)NOTE: PLEASE SHOW GROUNDING ATTACHMENT
 AT THE DETACHED STRUCTURE. BLDG/SLAB
 STEEL AND COLD WATER BOND. PER 250-50
  
 3)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN
 AS EXISTING FOR 200AMP SERVICE??? #1 IS
 NOT LARGE ENOUGH FOR 200A SERVICE.
 PLEASE SUBMIT CLARIFICATION. IF #1 THEN
 MAIN SERVICE CONDUCTORS WILL BE REQ`D TO
 BE BROUGHT UP TO CODE.
  
 4)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ASLL SLEEPING ROOMS.THIS INCLUDE
 -S CABANA, AS IT HAS A CLOSET AND BATH
 FOR SLEEPING ROOM CONVERSION.
 ALL MUST BE WIRED INLINE.
  
 5)NOTE; PLEASE PROVIDE PANEL SCHEDULES
 FOR EXISTING AND NEW PANEL. PLEASE LIST
 THE REQ`D BATH(S) CIRCUIT(S) PER 210-52D
 AND 210-11-C-3. MUST BE #12 AWG AND 20A.
  
 6)NOTE: PLEASE NOET MISSING OUTLET FOR
 NEW SECOUND FLOOR BATH REQ`D BY 210-52D
  
 7)(NOTE: PLEASE NOTE MISSING EGRESS
 LIGHT REQ`D FOR CABANA PER 210-70.
  
 8)NOTE: PLEASE NOTE ELECTRICAL PANEL
 SHOWN IN CABANA CLOSET. THIS IS NOT
 PERMITTED IN CLOSET SPACE PER 110-26F
 AND 384-7 FOR ELECTRICAL EQUIPMENT BEING
 INSTALLED AROUND IGNITABLE MATERIALS.
  
 9)NOTE: PLEASE CLARIFY 240/1%%C SHOWN ON
 BOTTOM OF LOAD CALCULATIONS. (TYPE-O)???
  
 10)NOTE: SPACE HEATER SHOWN ON LOAD
 CALCULATIONS FOR CABANA? NOT SHOWN ON
 ELECTRICAL FLOOR PLAN???? PLEASE CALRIFY
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THEREARE ANY QUESITONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372