| Plan Review Notes For Permit 00091113 |
| Permit Number |
00091113 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | 1. PROVIDE PRODUCT APPROVAL INFORMATION | | | ON PYROSCAT INSULATION. INCLUDE INSTALL- | | | ATION DETAILS. | | | 2. ENTIRE DUCT LENGTH TO BE PROTECTED | | | PER 1997 SMC 505.9.1 "ALL VERTICAL AND | | | HORIZONTAL DUCTS LOCATED WITHINN A BUILD | | | ING OF TWO STORIES OR MORE SHALL BE | | | ENCLOSED IN A CONTINUOUS ENCLOSURE | | | \\EXTENDING FROM THE CEILING ABOVE THE | | | HOOD TO OR THROUGH THE ROOF." PROVIDE | | | DETAILS ON METHOD OF COMPLIANCE TO BE | | | USED. | | | PROVIDE INFORMATION ON HOW RESIDUE TRAP | | | WILL EXTEND THROUGH ABOVE ENCLOSURE AND | | | HOW MAINTAINANCE WILL OCCUR TO PREVENT | | | BUILDUP AT THIS LOCATION. |
|