| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | | | | 1)NOTE: PLEASE SEE 230-72 FOR GROUPING | | | OF MAIN DISCONNECTS. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL EQUIPMENT BEING INSTALLED. | | | PLEASE SEE 110-9/ 215-5 | | | ALL MAINS/PANELS/BREAKERS MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|