Plan Review Notes
Plan Review Notes For Permit 00091048
Permit Number 00091048
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) ENTIRE GENERATOR ROOM IS TO BE
 CONSTRUCTED WITH AT LEAST A TWO HOUR
 FIRE RATING. OPENINGS IN WALLS TO BE
 AT LEAST 1 1/2 FIRE RATED. PLEASE
 PROVIDE TESTED TWO HOUR RATED ASSEMBLY
 2) A RAISED SILL OF AT LEAST 4" HIGH
 SHALL BE PROVIDED AT DOOR OPENINGS.
 3) ALL FLOORS AND WALLS SHALL BE
 LIQUIDTIGHT.
 4) IF THE EXISTING MAINTENANCE BUILDING
 IS FIRE SPRINKLER PROTECTED, FIRE
 SPRINKLER COVERAGE IS TO BE EXTENDED
 INTO THE GENERATOR ROOM.
 5) PROVIDE MORE DETAILS ON EMERGENCY
 GENERATOR.