| Plan Review Notes For Permit 00091048 |
| Permit Number |
00091048 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) ENTIRE GENERATOR ROOM IS TO BE | | | CONSTRUCTED WITH AT LEAST A TWO HOUR | | | FIRE RATING. OPENINGS IN WALLS TO BE | | | AT LEAST 1 1/2 FIRE RATED. PLEASE | | | PROVIDE TESTED TWO HOUR RATED ASSEMBLY | | | 2) A RAISED SILL OF AT LEAST 4" HIGH | | | SHALL BE PROVIDED AT DOOR OPENINGS. | | | 3) ALL FLOORS AND WALLS SHALL BE | | | LIQUIDTIGHT. | | | 4) IF THE EXISTING MAINTENANCE BUILDING | | | IS FIRE SPRINKLER PROTECTED, FIRE | | | SPRINKLER COVERAGE IS TO BE EXTENDED | | | INTO THE GENERATOR ROOM. | | | 5) PROVIDE MORE DETAILS ON EMERGENCY | | | GENERATOR. |
|