2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT CLARIFICATION ON
 GENERATOR.MORETHAN SIX THROWS ON THE
 MDP? PLEASE SHOW MORE DETAIL ON FEEDERS
 GOING TO EACH BLDG. PER LOCAL AMENDMENTS
 NO MORE THAN 8` OF UNPROTECTED CONDUCTOR
 -S PERMITTED INSIDE BLDG.?? NEED TO
 SHOW.
 PLEASE SEE REQ`MENTS FOR LABELING OF
 ALL BLDG. DISCONNECTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ANY QUESTIONS/INSIGHT
 ON THIS INSTALLATION PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372