| Plan Review Notes For Permit 00091035 |
| Permit Number |
00091035 |
|
| Review Stop |
R |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2002-07-25 00:00:00 | BUTT GLAZING ASSEMBLY: | | | A)ENGINEER NEEDS TO PROVIDE COMPLETE | | | ENGINEERED ANALYSIS FOR THE COMPLETE | | | SITE SPECIFIC ASSEMBLY AS SHOWN ON THE | | | ARCHITECTURAL DRAWINGS. SEE SECTIONS | | | 2406.1 FOR DEFLECTION CALCULATIONS AND | | | SECTION 2406.2 FOR INFORMATION REQ'D | | | TO BE SUBMITTED BY THE ENGINEER. | | | B)ENGINEER TO PROVIDE COMPLETE SPECS FOR | | | SILICONE TO BE USED INCLUDING AT SIDE | | | WHERE GLASS IS BUTT TOGETHER. | | | C)THICKNESS OF GLASS SPECIFIED BY THE | | | ENGINEER DOESN'T MATCH THICKNESS SHOWN | | | ON PRODUCT APPROVAL FOR KDI 2000 FIXED | | | GLASS IMPACT WINDOW. | | | D)PROVIDE COPIES OF APPROVED DRAWINGS | | | FOR KDI 2000 FIXED GLASS IMPACT WINDOW | | | | | | REMAINDER: | | | ARCHITECT TO REVIEW ASSEMBLY PRIOR TO | | | SUBMITTAL. | | | | | | | | | SUGGESTION: | | | SEE SITE SPECIFIC ENGINEERING PACKAGE | | | SUBMITTED FOR ENTRY DOOR AS A SAMPLE OF | | | INFORMATION REQUIRED TO BE SUBMITTED. |
|