Plan Review Notes
Plan Review Notes For Permit 00091035
Permit Number 00091035
Review Stop R
Sequence Number 8
Notes
Date Text
2002-07-25 00:00:00BUTT GLAZING ASSEMBLY:
 A)ENGINEER NEEDS TO PROVIDE COMPLETE
 ENGINEERED ANALYSIS FOR THE COMPLETE
 SITE SPECIFIC ASSEMBLY AS SHOWN ON THE
 ARCHITECTURAL DRAWINGS. SEE SECTIONS
 2406.1 FOR DEFLECTION CALCULATIONS AND
 SECTION 2406.2 FOR INFORMATION REQ'D
 TO BE SUBMITTED BY THE ENGINEER.
 B)ENGINEER TO PROVIDE COMPLETE SPECS FOR
 SILICONE TO BE USED INCLUDING AT SIDE
 WHERE GLASS IS BUTT TOGETHER.
 C)THICKNESS OF GLASS SPECIFIED BY THE
 ENGINEER DOESN'T MATCH THICKNESS SHOWN
 ON PRODUCT APPROVAL FOR KDI 2000 FIXED
 GLASS IMPACT WINDOW.
 D)PROVIDE COPIES OF APPROVED DRAWINGS
 FOR KDI 2000 FIXED GLASS IMPACT WINDOW
  
 REMAINDER:
 ARCHITECT TO REVIEW ASSEMBLY PRIOR TO
 SUBMITTAL.
  
  
 SUGGESTION:
 SEE SITE SPECIFIC ENGINEERING PACKAGE
 SUBMITTED FOR ENTRY DOOR AS A SAMPLE OF
 INFORMATION REQUIRED TO BE SUBMITTED.