Plan Review Notes
Plan Review Notes For Permit 00091035
Permit Number 00091035
Review Stop R
Sequence Number 7
Notes
Date Text
2002-07-19 00:00:00CHECKLIST:
 1-BUTT GLAZING ASSEMBLY:
 A)INFORMATION SUBMITTED DOESN'T SATISFY
 REQUIREMENTS OF SEC. 2406.2 SBC 1997
 AS REQUESTED ON PREVIOUS CHECKLIST.
 **"DETAILED SHOP DRAWINGS,SPECIFICATIONS
 AND RATIONAL ANALYSIS AND/OR TEST DATA
 ASSURING SAFE PERFORMANCE FOR THE
 SPECIFIC INSTALLATION SHALL BE
 PREPARED BY ENGINEERS EXPERIENCED IN
 THIS WORK AND SHALL BE SUBMITTED FOR
 AND RECEIVE, IF WARRANTED, FORMAL
 APPROVAL BY THE BUILDING OFFICIAL."
 B)INFORMATION SUBMITTED IS CROSS
 MATCHING TWO DIFFERENT CODES STANDARD
 BUILDING CODE AND FLORIDA BUILDING
 CODE. ALSO, NEED TO SPECIFY THE YEAR
 OF THE CODE USED.
 C)DESIGN PRESSURES SPECIFIED DON'T MATCH
 THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT.
 D)MEAN ROOF HEIGHT IS INCORRECT. ENG'R
 NEEDS TO SEE ARCHITECT'S PLANS TO
 PROPERLY DESIGN SITE SPECIFIC ASSEMBLY
 E)WHERE IS THE ATTACHED SPECIFICATION
 MENTIONED ON ENGINEER LETTER?
  
 2-SUBMITTED PRODUCT APPROVAL FOR FIXED
 WINDOWS IS FOR RECTANGULAR WINDOWS NOT
 FOR ARCHED WINDOWS. THIS PRODUCT
 APPROVAL WAS ALREADY SUBMITTED FOR THE
 RECTANGULAR WINDOWS AND IT WAS BY PGT
 WINDOWS NOT BY K.D WINDOWS. CLARIFY,
 WHICH ONE WAS INSTALLED.
  
 3-ARCHITECT TO REVIEW AND APPROVE SITE
 SPECIFIC ASSEMBLY PRIOR TO SUBMITTAL.
  
 NOTE: PRODUCT APPROVAL FOR FRENCH DOORS
 WITH SIDELITES IS OK.