| 2002-07-19 00:00:00 | CHECKLIST: |
| | 1-BUTT GLAZING ASSEMBLY: |
| | A)INFORMATION SUBMITTED DOESN'T SATISFY |
| | REQUIREMENTS OF SEC. 2406.2 SBC 1997 |
| | AS REQUESTED ON PREVIOUS CHECKLIST. |
| | **"DETAILED SHOP DRAWINGS,SPECIFICATIONS |
| | AND RATIONAL ANALYSIS AND/OR TEST DATA |
| | ASSURING SAFE PERFORMANCE FOR THE |
| | SPECIFIC INSTALLATION SHALL BE |
| | PREPARED BY ENGINEERS EXPERIENCED IN |
| | THIS WORK AND SHALL BE SUBMITTED FOR |
| | AND RECEIVE, IF WARRANTED, FORMAL |
| | APPROVAL BY THE BUILDING OFFICIAL." |
| | B)INFORMATION SUBMITTED IS CROSS |
| | MATCHING TWO DIFFERENT CODES STANDARD |
| | BUILDING CODE AND FLORIDA BUILDING |
| | CODE. ALSO, NEED TO SPECIFY THE YEAR |
| | OF THE CODE USED. |
| | C)DESIGN PRESSURES SPECIFIED DON'T MATCH |
| | THE DESIGN PRESSURES CALCULATED BY THE |
| | ARCHITECT. |
| | D)MEAN ROOF HEIGHT IS INCORRECT. ENG'R |
| | NEEDS TO SEE ARCHITECT'S PLANS TO |
| | PROPERLY DESIGN SITE SPECIFIC ASSEMBLY |
| | E)WHERE IS THE ATTACHED SPECIFICATION |
| | MENTIONED ON ENGINEER LETTER? |
| | |
| | 2-SUBMITTED PRODUCT APPROVAL FOR FIXED |
| | WINDOWS IS FOR RECTANGULAR WINDOWS NOT |
| | FOR ARCHED WINDOWS. THIS PRODUCT |
| | APPROVAL WAS ALREADY SUBMITTED FOR THE |
| | RECTANGULAR WINDOWS AND IT WAS BY PGT |
| | WINDOWS NOT BY K.D WINDOWS. CLARIFY, |
| | WHICH ONE WAS INSTALLED. |
| | |
| | 3-ARCHITECT TO REVIEW AND APPROVE SITE |
| | SPECIFIC ASSEMBLY PRIOR TO SUBMITTAL. |
| | |
| | NOTE: PRODUCT APPROVAL FOR FRENCH DOORS |
| | WITH SIDELITES IS OK. |