2002-05-03 00:00:00CHECKLIST:
 1-INFORMATION REQUESTED ON PROVISO DATED
 11-29-00 WAS NEVER SUBMITTED FOR
 REVIEW.
 2-SUBMITTAL FOR SITE SPECIFIC PRODUCT
 APPROVAL FOR ENTRY DOORS ASSEMBLY:
 A)INFORMATION DOESN'T MATCH BUILDING
 CODE USED BY ARCHITECT WHO DESIGNED
 THE BUILDING.(SBC 1997 NOT FBC 2001).
 B)DESIGN PRESSURES USED DON'T MEET THE
 DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT.
 C)AS PER BLDG OFFICIAL: SITE SPECIFIC
 INSTALLATIONS REQUIRES PROFESSIONAL OF
 RECORD TO REVIEW "PRODUCT APPROVAL"
 ENGINEERING INFORMATION AND CERTIFY
 (SIGNED AND SEALED) THAT SUCH PRODUCT
 WILL BE STRUCTURALLY ADEQUATE TO BE
 INSTALLED IN THE STRUCTURE HE DESIGNED
 D)WRONG PROJECT ADDRESS. REVISE AS REQ'D
 NOTE: ENGINEER'S CALCULATIONS SHOW THAT
 HE CONSIDERS DOOR ASTRAGAL AND DEAD
 BOLT TO SATISFY HIS CALCULATIONS.
 NEED TO CHECK THAT THIS LOCKS WILL
 COMPLY WITH EGRESS REQUIREMENTS TO
 AVOID CONFLICTS.