| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE FRAMING DETAILS FOR |
| | CUPOLAS.CLEARLY SPECIFY ALL CONNECTORS |
| | AND FRAMING AROUND ARCHED WINDOWS. |
| | SEC. 104.2.2 CITY AMENDMENTS. |
| | 2-REVISE THE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM: THE |
| | MEAN ROOF HEIGHT AND BASIC VELOCITY |
| | PRESSURE DON'T MATCH. SEE TABLE |
| | 1606.2A OF SBC 1997. |
| | 3-SOIL TEST REPORT SHOWS THE PRESENCE OF |
| | ROOTS AND ORGANIC MATERIALS. THE AREA |
| | UNDER FOOTINGS, FOUNDATIONS AND |
| | CONCRETE SLABS ON GRADE SHALL HAVE ALL |
| | VEGETATION, STUMPS, ROOTS AND FOREIGN |
| | MATERIALS REMOVED PRIOR TO CONSTRUCT'N |
| | SECTION 1804.1.8 SBC 1997. |
| | 4-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ENTRY DOORS: 3"-0" BY 9'-0" WITH |
| | SIDELITES ASSEMBLY. |
| | B)FRENCH DOORS WITH SIDELITES ASSEMBLY. |
| | C)ARCHED WINDOWS |
| | D)COMPLETE BUTT GLAZING ASSEMBLY. |
| | 5-PROVIDE COMPLETE INFORMATION FOR GLASS |
| | MISSILE IMPACT PROTECTION FOR THIS |
| | HOUSE. EG: PROVIDE A KEY PLAN SHOWING |
| | AREAS TO HAVE IMPACT GLAZING AND AREAS |
| | TO HAVE ANY OTHER PROTECTION. |
| | -PROVIDE COMPLETE INFORMATION FORSUCH |
| | OTHER METHOD OF PROTECTION. |
| | 6-SEE PLANS FOR ADDITIONAL COMMENTS. |
| | |
| | |
| | |