| Plan Review Notes For Permit 00091035 |
| Permit Number |
00091035 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SHT.A-1-NOTE #7-SHOWER HEADS SHALL BE | | | LIMITED TO A MAX.OF 2.5GPM PER F.E.C. | | | SEC.612.1.ABC.2.4. | | | | | | 2)DRY VENTS NOT PERMITTED PER SPC SEC. | | | 906.2.1. | | | | | | 3)LOCATION OF FIXTURES SHALL NOT INTER- | | | FERE W/THE OPERATION OF DOORS,WINDOWS, | | | ETC.PER SPC SEC.404.2.SEE M.B.,POWDER | | | ROOM AND CABANA BATH. | | | | | | 4)PLEASE PUT CALCULATIONS FOR COMBUSTION | | | AIR ON THE PLANS,NOT ON THE MANUF.SHEETS | | | CALCULATIONS SHALL BE DONE BY THE DESIGN | | | PROFESSIONAL.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.104.2.3. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|