2001-01-08 00:00:001)SHT.A-1-NOTE #7-SHOWER HEADS SHALL BE
 LIMITED TO A MAX.OF 2.5GPM PER F.E.C.
 SEC.612.1.ABC.2.4.
  
 2)DRY VENTS NOT PERMITTED PER SPC SEC.
 906.2.1.
  
 3)LOCATION OF FIXTURES SHALL NOT INTER-
 FERE W/THE OPERATION OF DOORS,WINDOWS,
 ETC.PER SPC SEC.404.2.SEE M.B.,POWDER
 ROOM AND CABANA BATH.
  
 4)PLEASE PUT CALCULATIONS FOR COMBUSTION
 AIR ON THE PLANS,NOT ON THE MANUF.SHEETS
 CALCULATIONS SHALL BE DONE BY THE DESIGN
 PROFESSIONAL.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.