| Plan Review Notes For Permit 00091007 |
| Permit Number |
00091007 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)CLEARLY SHOW LOCATION OF EACH GAS | | | APPLIANCE ON THE PLAN.COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1. | | | | | | 2)SUBMIT DIMENSIONS OF ROOM HOUSING THE | | | WATER HEATER AND THE OTHER UNIDENTIFIED | | | APPLIANCE.COMPLY W/SGC SEC.402.4.1FOR | | | COMBUSTION AIR.SEE SECS.402.4.4.1 THRU | | | 402.4.4.4. | | | | | | 3)CLARIFY BI-FOLD DOOR DIMENSIONS FOR | | | THE LOUVERS.IS THE LOUVERED AREA | | | 36"X12"?COMPLY W/SGC SECS.402.4.4. | | | | | | 4)SUBMIT A GAS RISER DIAGRAM THAT | | | CLEARLY DEPICTS THE ROUTING OF THE PIPE. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 5)TANK SHALL BE MIN.10' FROM SOURCE OF | | | IGNITION PER NFPA 58,SEC. | | | | | | 6)INDICATE TYPE OF PIPING FROM TANK TO | | | 2ND STAGE REGULATOR. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|