| Date |
Text |
| 2001-01-08 00:00:00 | 1)SHT.12-REVISE REFERENCE TO "A"COPPER. |
| | THERE IS NO SUCH CLASSIFICATION. |
| | |
| | 2)CONTACT ROD COMPO AT 561-835-7423 FOR |
| | REQS.FOR THE GREASY WASTE SYSTEM.SUBMIT |
| | A COPY OF APPROVAL FORM FROM WPB |
| | UTILITIES.MIN.SIZE GREASE TRAP TO BE 750 |
| | GALS.COUNTYWIDE AMEND.101.4.7. |
| | |
| | 3)SUBMIT PIPING DIAGRAMS FOR AIR AND |
| | WATER LINES.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1. |
| | |
| | 4) MIN.SIZE OF BUILDING SEWER SHALL BE |
| | 4"PER SPC SEC.714.1 FOOTNOTE #2.(SHT.P-1 |
| | |
| | 5)ALL PLUMBING WORK NOT INSTALLED BY THE |
| | BUILING SUPPLIER SHALL BE DONE BY THE |
| | LICENSED PLUMBING CONTRACTOR.F.S.CHAPT. |
| | 468.SEE SHTS.SC-1,P-1,P-3,AND NOTES. |
| | PLANS NOTE WORK TO BE DONE BY GC |
| | |
| | 6)DRAINS FOR INDIRECT WASTES INSTALLED |
| | IN FIELD SHALL BE FLOOR SINKS NOT FLOOR |
| | DRAINS OR FUNNEL DRAINS.SPC SEC.804.1. |
| | |
| | 7)SUBMIT ADDITIONAL INFORMATION ON LP |
| | TANK STORAGE.SHOW TOTAL AGGREGATE |
| | CAPACITY,LOCATION OF ANY SOURCES OF |
| | IGNITION,LOCATION OF TANKS IN PROXIMITY |
| | TO BUILDING OPENINGS,ETC.COMPLY W/NFPA |
| | 58 SEC.3-2.2.2.AND TABLE 3-2.2.2. |
| | |
| | 8)COMPLY W/ATTACHED LIST OF REQS.FOR GAS |
| | DRAWINGS. |
| | |
| | 9)HEAT TRAPS ARE REQD.ON THE WATER |
| | HEATERS PER F.E.C.SEC.412.1.ABCD.2.1.3. |
| | |
| | 10)WATER HEATER SHALL BE READILY |
| | ACCESSIBLE PER SPC SEC.501.7.SUPPLY |
| | SHIP'S LADDER AND PLATFORM OR RELOCATE |
| | TO FLOOR. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |