2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED ON
 PLANS. SHOULD READ NFPA 101-LIFE SAFETY
 CODE, 1985 INSTEAD OF 1994.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 3) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 4) SERVICE STATION TO COMPLY WITH THE
 REQUIREMENTS OF NFPA 30A, THE STANDARD
 FOR AUTOMOTIVE AND MARINE SERVICE
 STATION CODE, AND UNIFORM FIRE SAFETY
 RULES AND STANDARDS, CHAPTER 4A-49.
 5)THE UNDERGROUND FUEL TANKS ARE TO
 COMPLY WITH NFPA 30, THE STANDARD FOR
 THE STORAGE AND HANDLING OF COMBUSTIBLE
 LIQUIDS.
 6) PLEASE INDICATE ON THE PLANS, THE
 LENGTHS OF FUEL HOSES PLANNED FOR USE.
 7) PLEASE IDENTIFY TYPE SIGNAGE FOR
 EMERGENCY SHUT OFFS FOR FUEL DISPENSING
 EQUIPMENT.
 8) PLEASE IDENTIFY THE LOCATIONS FOR
 WARNING SIGNS AT THE FUEL DISPENSING
 AREA. WHAT WORDING IS PLANNED FOR THESE
 SIGNS.
 9) PLEASE INDICATE BREAKAWAY DEVICE
 LOCATIONS.
 10) PLEASE INDICATE TYPES AND LOCATIONS
 OF FIRE EXTINGUISHERS.
 11) PLEASE PROVIDE LISTING INFORMATION
 ON DEVICES PLANNED FOR USE AT FUEL
 DISPENSING AREA.
 12) PLEASE PROVIDE INFORMATION ON
 PROPANE STORAGE AREA.
 13) PLEASE PROVIDE FLAME SPREAD
 CHARACTERISTICS ON CANOPY.