| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED ON |
| | PLANS. SHOULD READ NFPA 101-LIFE SAFETY |
| | CODE, 1985 INSTEAD OF 1994. |
| | 2) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWINGS. BUILDING ADDRESS TO |
| | COMPLY WITH CITY CODE REQUIREMENTS. |
| | 3) GAS INSTALLATION TO COMPLY WITH |
| | NFPA 54. |
| | 4) SERVICE STATION TO COMPLY WITH THE |
| | REQUIREMENTS OF NFPA 30A, THE STANDARD |
| | FOR AUTOMOTIVE AND MARINE SERVICE |
| | STATION CODE, AND UNIFORM FIRE SAFETY |
| | RULES AND STANDARDS, CHAPTER 4A-49. |
| | 5)THE UNDERGROUND FUEL TANKS ARE TO |
| | COMPLY WITH NFPA 30, THE STANDARD FOR |
| | THE STORAGE AND HANDLING OF COMBUSTIBLE |
| | LIQUIDS. |
| | 6) PLEASE INDICATE ON THE PLANS, THE |
| | LENGTHS OF FUEL HOSES PLANNED FOR USE. |
| | 7) PLEASE IDENTIFY TYPE SIGNAGE FOR |
| | EMERGENCY SHUT OFFS FOR FUEL DISPENSING |
| | EQUIPMENT. |
| | 8) PLEASE IDENTIFY THE LOCATIONS FOR |
| | WARNING SIGNS AT THE FUEL DISPENSING |
| | AREA. WHAT WORDING IS PLANNED FOR THESE |
| | SIGNS. |
| | 9) PLEASE INDICATE BREAKAWAY DEVICE |
| | LOCATIONS. |
| | 10) PLEASE INDICATE TYPES AND LOCATIONS |
| | OF FIRE EXTINGUISHERS. |
| | 11) PLEASE PROVIDE LISTING INFORMATION |
| | ON DEVICES PLANNED FOR USE AT FUEL |
| | DISPENSING AREA. |
| | 12) PLEASE PROVIDE INFORMATION ON |
| | PROPANE STORAGE AREA. |
| | 13) PLEASE PROVIDE FLAME SPREAD |
| | CHARACTERISTICS ON CANOPY. |