Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SEE 210-63 FOR REQ`MENT
 OF GFI ON ROOF.
  
 2)NOTE: PLEASE SEE 210-62 FOR SHOW
 WINDOW RECEPTS. 220-12A
  
  
 3)NOTE: PLEASE SEE 220-12B FOR TRACK
 LIGHTING LOAD CALCULATIONS. PLEASE SHOW
  
 4)NOTE: PLEASE SEE 250-50. WHERE AVAIL-
 -ABLE BLDG. STEEL ALSO FOR GROUNDING
 ELECTRODE CONDUCTOR. NEW CONTRUCTION.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372