| Plan Review Notes For Permit 00090956 |
| Permit Number |
00090956 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL | | | BRANCH CIRCUIT #`S ON PLAN AND CORRELATE | | | WITH PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE SHOW ALL TRACK LIGHTING | | | CALCULATIONS PER 220-12B. | | | | | | 3)NOTE: PLEASE SEE PANEL SCHEDULE AND | | | RISER DIAGRAM. ONE SHOWS 4/0 AND THE | | | OTHER SHOWS 3-#4`S. PLEASE CORRECT. | | | | | | 4)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | AT 125% (LIGHTING) ETC. | | | | | | 5)NOTE: PLEASE CLARIFY OUTLETS SHOWN AS | | | C.O.? | | | | | | 6)NOTE: PLEASE SHOW ALL THE REQ`MENTS | | | FOR SPRAY BOOTH PER 516-2. PLEASE | | | PROVIDE CLEARENCES ON PLANS. | | | | | | 7)NOTE: PLEASE CLARIFY THE REQ`D SHOW | | | WINDOW OUTLETS PER 210-62 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|