| Notes |
| Date |
Text |
| 2001-05-01 00:00:00 | BUILDING PROVISO: | | | 1)- ALL EXTERIOR DOORS AND WINDOWS RE- | | | QUIRE PRODUCT | | | BUILDING PLAN REVIEW | | | | | | 1)- ALL EXTERIOR DOORS & WINDOWS RE- | | | QUIRE PRODUCT TESTING FOR 110 MILE PER | | | HOUR WIND. THE CITY ACCEPTS DADE COUNTY | | | OR SBCCI PRODUCT REPORTS (CURRENT & 2 | | | COPIES FOR EACH TYPE OPENING). | | | SBC 1606.2.6.2. | | | | | | 2)- LARGE MISSLE IMPACT TESTING FOR ALL | | | GLAZED OPENINGS, EITHER TESTING FOR | | | WINDOWS OR STORM SHUTTERS. | | | | | | 3)- ROOFING ALSO REQUIRES TESTING FOR | | | 110 HPH WIND 1503.3.2/ 1503.4.1.2. | | | | | | 4)- BI-FOLD DOORS FOR THE LAUNDRY ROOM | | | WILL NOT MAKE THE 110 MPH WIND ZONE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|