| Plan Review Notes For Permit 00090869 |
| Permit Number |
00090869 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1.FIRE ALARM SYSTEM SHALL BE CLASS A OR | | | ADDRESSABLE. | | | 2.INDICATE LOCATION OF PROTECTED MEANS | | | OF EGRESS FROM 2ND AND 3RD FLOORS. | | | 3.PROVIDE EXIT LIGHT AND EMERGENCY LIGHT | | | LOCATIONS THROUGHOUT. | | | 4.PROVIDE DETAILS OF RATED STAIR ENCLOSU | | | RE. (WALLS AND SELF CLOSING DOORS) |
|