2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE CALL FOR CORRECT LIST OF
 CURRENT CODES WE ARE UNDER. NOT ALL ON
 COVER SHEET ARE CORRECT.
  
 THE "99" NEC APPLIES FOR ELECTRICAL.
  
 2)NOTE: PLEASE CLARIFY ALL ELECTRICAL
 WORK ONLY BEING DONE FOR SHELL???
 SHOW ALL MIN EGRESS LIGHTING FOR ALL
 FLOORS AND EMERGENCY/EXIT LIGHTING
 REQ`D BY NFPA./LIFE SAFETY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  