| Plan Review Notes For Permit 00090820 |
| Permit Number |
00090820 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)PLANS SHALL BE SUBMITTED SEPARATELY | | | FOR EACH BUILDING UNDER THE APPLICABLE | | | PERMIT NUMBER ASSIGNED TO SUCH BUILDING. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.1.5 | | | 104.2.1. | | | | | | 2)SHT.A-G3.01-CLEARLY SHOW SIZE OF GAS | | | LINES/PIPING LOCATED AT BOTH METERS. | | | ALL COLUMN LINES SHALL BE LEGIBLE TO | | | DETERMINE LOCATION OF METERS.SGC SEC.301 | | | & COUNTYWIDE AMENDMENTS TO SPC SEC.104.2 | | | | | | 3)SHTS.B-G3.01,3.02-GAS PIPING APPEARS | | | TO BE LOCATED IN STAIR ENCLOSURE.THIS IS | | | NOT PERMITTED PER SBC 1006.1.3, | | | 1006.1.3.1. | | | | | | 4)SHT.B-G3.01-GAS METERS SHALL BE A MIN. | | | OF 3' FROM ANY SOURCE OF IGNITION.CHECK | | | ALL GAS METERS AND IDENTIFY ANY SOURCES | | | OF IGNITION.(E.G.-TRANSFORMERS)NFPA 54 | | | SEC.2.7.2. | | | | | | 5)SHT.C-G3.01-CLEARLY SHOW ON THE PLAN | | | THAT THE GAS LINES ARE NOT INSTALLED | | | WITHIN THE STAIR ENCLOSURE.SBC SEC. | | | 1006.1.3. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|