Plan Review Notes
Plan Review Notes For Permit 00090820
Permit Number 00090820
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)PLANS SHALL BE SUBMITTED SEPARATELY
 FOR EACH BUILDING UNDER THE APPLICABLE
 PERMIT NUMBER ASSIGNED TO SUCH BUILDING.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.1.5
 104.2.1.
  
 2)SHT.A-G3.01-CLEARLY SHOW SIZE OF GAS
 LINES/PIPING LOCATED AT BOTH METERS.
 ALL COLUMN LINES SHALL BE LEGIBLE TO
 DETERMINE LOCATION OF METERS.SGC SEC.301
 & COUNTYWIDE AMENDMENTS TO SPC SEC.104.2
  
 3)SHTS.B-G3.01,3.02-GAS PIPING APPEARS
 TO BE LOCATED IN STAIR ENCLOSURE.THIS IS
 NOT PERMITTED PER SBC 1006.1.3,
 1006.1.3.1.
  
 4)SHT.B-G3.01-GAS METERS SHALL BE A MIN.
 OF 3' FROM ANY SOURCE OF IGNITION.CHECK
 ALL GAS METERS AND IDENTIFY ANY SOURCES
 OF IGNITION.(E.G.-TRANSFORMERS)NFPA 54
 SEC.2.7.2.
  
 5)SHT.C-G3.01-CLEARLY SHOW ON THE PLAN
 THAT THE GAS LINES ARE NOT INSTALLED
 WITHIN THE STAIR ENCLOSURE.SBC SEC.
 1006.1.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.