| Plan Review Notes For Permit 00090510 |
| Permit Number |
00090510 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-07-21 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT ELECTRICAL | | | RISER DIAGRAM SHOWS TAPS FROM THE TRANS- | | | -FORMER BEING TAPPED? PLEASE NOTE THAT | | | THESE TWO PANELS MAY BE FED WITH TWO | | | SEPARATE RUNS FROM THE TRANSFORMER BUT | | | NOT INTO A GUTTER AND THEN TAPPED AGAIN. | | | 240-21 | | | *TRANSFORMER CAN HAVE LUGS RATED FOR | | | MORETHAN ONE WIRE* | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | | SIGNED, DATED OR SEALED BY THE ENGINEER | | | OF RECORD PER FS,FAC 471.025. | | | PLEASE ALSO NOTE THAT TWO DIFFERENT | | | SETS OF PLANS WERE SUBMITTED?? | | | PLEASE CORRELATE AND SUBMIT. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|