Plan Review Notes
Plan Review Notes For Permit 00090510
Permit Number 00090510
Review Stop E
Sequence Number 3
Notes
Date Text
2001-07-21 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ELECTRICAL
 RISER DIAGRAM SHOWS TAPS FROM THE TRANS-
 -FORMER BEING TAPPED? PLEASE NOTE THAT
 THESE TWO PANELS MAY BE FED WITH TWO
 SEPARATE RUNS FROM THE TRANSFORMER BUT
 NOT INTO A GUTTER AND THEN TAPPED AGAIN.
 240-21
 *TRANSFORMER CAN HAVE LUGS RATED FOR
 MORETHAN ONE WIRE*
  
 2)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 SIGNED, DATED OR SEALED BY THE ENGINEER
 OF RECORD PER FS,FAC 471.025.
 PLEASE ALSO NOTE THAT TWO DIFFERENT
 SETS OF PLANS WERE SUBMITTED??
 PLEASE CORRELATE AND SUBMIT.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372