| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED ON | | | T-1. SHOULD READ NFPA 101, LIFE SAFETY | | | CODE, 1985 EDITION. | | | 2) INTERIOR FINISHES NEED TO BE NOTED | | | ON PLANS. | | | 3) NO HYDRAULIC CALCULATIONS PROVIDED | | | FOR FIRE SPRINKLER DRAWINGS INCLUDED | | | IN PLANS. | | | 4) DRAFT STOP IS TO BE 18" NON | | | COMBUSTIBLE WITH FIRE SPRINKLER HEADS NO | | | FARTHER APART THAN 6' FEET. | | | 5) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA 101 REQUIREMENTS FOR SAME. | | | 6) HEADROOM IN MEANS OF EGRESS TO BE | | | 7'-6" OR 6'-8 WITH PROJECTIONS FROM | | | CEILING. | | | 7) PROVIDE SEPARATE PLANS AND PERMIT | | | FOR FIRE ALARM EQUIPMENT SHOWN ON PLANS. |
|