2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED ON
 T-1. SHOULD READ NFPA 101, LIFE SAFETY
 CODE, 1985 EDITION.
 2) INTERIOR FINISHES NEED TO BE NOTED
 ON PLANS.
 3) NO HYDRAULIC CALCULATIONS PROVIDED
 FOR FIRE SPRINKLER DRAWINGS INCLUDED
 IN PLANS.
 4) DRAFT STOP IS TO BE 18" NON
 COMBUSTIBLE WITH FIRE SPRINKLER HEADS NO
 FARTHER APART THAN 6' FEET.
 5) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101 REQUIREMENTS FOR SAME.
 6) HEADROOM IN MEANS OF EGRESS TO BE
 7'-6" OR 6'-8 WITH PROJECTIONS FROM
 CEILING.
 7) PROVIDE SEPARATE PLANS AND PERMIT
 FOR FIRE ALARM EQUIPMENT SHOWN ON PLANS.