| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1.PROVIDE SQUARE FOOTAGE OF AREA UNDER | | | CONTRACT IN ORDER TO CACULATE OCCUPANT | | | LOAD.TABLE 1003.1 | | | 2.PROVIDE PLANS AND DETAILS FOR 4TH | | | FLOOR ROOM. | | | 3. PROVIDE DETAILS FOR STAIRS TO 4TH | | | FLOOR ROOM " TREADS AND RISERS" | | | 4.SHEET A-1A DETAILS 8&9 REFRENCES EXIST | | | -ING RATED WALLS SUBMIT DETAIL SHOWING | | | UL RATING. | | | 5.SHEET A-1A DETAIL 10 REFERENCES GYPSUM | | | BOARD AND METAL STUD WALL SUBMIT SHOWING | | | UL# FOR TENANT SEPARATION. | | | 6.EXIT DOOR # 308 SWINGS WRONG DIRECTION | | | SECTION 1012.1.2 SBC 1997 EDITION | | | 7.EXIT DOOR LOCATION MUST COMPLY WITH | | | SECTION 1004.1.4 SBC 1997 EDITION | | | 8.SUBMIT RATING ON DOORS PER SECTION | | | 705.1.2 SBC 1997 EDITION. | | | 9.DEAD END CORRIDORS OVER 20 FEET ARE | | | NOT ALLOWED "CORRIDOR 306" SECTION | | | 1005.2 AND TABLE 1004 | | | 10. BUILDING IS CONSTRUCTION TYPE 2 ALL | | | LUMBER USED MUST COMPLY TO SECTION 6&7 | | | SBC 1997 EDITION. |
|