| Plan Review Notes For Permit 00090413 |
| Permit Number |
00090413 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-03-14 00:00:00 | DENIED; | | | | | | 1.FLOORSHALL BE USED INPLACE OF A HUB | | | DRAIN. FLOOR DRAIN SHALL BE PRIMED. | | | | | | 2.SHEET A-1 WATER HEATER IS IN A DIRRENT | | | LOCATION THAN P-3.1 AND NOT SHOWD AT | | | ALL ON P-2.1. | | | | | | 3.P-5 FLOOR DRAIN IN BATHROOM IS MISSING | | | FROM SANITARY RISER DIAGRAM. | | | | | | 4.WHY IS A MECHANICAL VENT NEEDED? TEN | | | FEET OF PIPE ABOVE THE CEILING AND THE | | | PLUMBER COULD TIE INTO THE VENT SYSTEM | | | | | | | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|