| Plan Review Notes For Permit 00090261 |
| Permit Number |
00090261 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE ART:S 230-76 AND 230- | | | -79 FOR THE REQ`DDISCONNECTING MEANS | | | SHUNT TRIP IS NOT A SERVICE RATED DISC. | | | | | | 2)NOTE: PLEASE SEE 230-72 FOR GROUPING | | | OF SERVICE DISCONNECTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|