Plan Review Notes
Plan Review Notes For Permit 00090202
Permit Number 00090202
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEW CODE REFERENCES
 SPC 94SGC 97FACBC 97
 (1) SHTS P-1,P-2 SHOW OCCUPANCY LOAD AS
 REQUIRED,TAB 407 MIN. NUMBER FACILITIES.
 SHOW REST RM LAY OUT W/ DEMINSIONS AND
 ELEVATIONS TO COMPLY W/FACBC SEC 4.22
 (2)PROVIDE KITCHEN EQUIPMENT DRWGS.
 (3) CONTACT WPB REGIONAL SEWER PLANT
 RODNEY COMPO 561-835-7423 FOR APPROVAL,
 GREASE TANK,SIZE,LOCATION AND CUT SHTS.
 (4) REST RM'S (S-1) W/C P-1 NOT VENTED,
 SHOW DWV PIPE SIZES FOR THIS BRANCH.
 TRAP PRIMER WATER SUPPLY TO A PLUMBING
 FIXTURE IN THE SAME ROOM.SEC 409.4
 (5)LOCATION AND SIZE OF WTR HTR,ENERGY
 TYPE.SEC 104.2
 (6) THIS IS THE THIRD TIME IN FOR PLAN
 REVIEW,PLEASE COMPLY WITH PREVIOUS
 COMMENTS AND ABOVE COMMENTS,ATTACHED.
 QUESTIONS CONTACT PAUL SCHMITZ
 561-659 8096 X 8233
 SEE ATTACHED GAS PIPING REQUIRMENTS.