| Plan Review Notes For Permit 00090202 |
| Permit Number |
00090202 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW CODE REFERENCES | | | SPC 94SGC 97FACBC 97 | | | (1) SHTS P-1,P-2 SHOW OCCUPANCY LOAD AS | | | REQUIRED,TAB 407 MIN. NUMBER FACILITIES. | | | SHOW REST RM LAY OUT W/ DEMINSIONS AND | | | ELEVATIONS TO COMPLY W/FACBC SEC 4.22 | | | (2)PROVIDE KITCHEN EQUIPMENT DRWGS. | | | (3) CONTACT WPB REGIONAL SEWER PLANT | | | RODNEY COMPO 561-835-7423 FOR APPROVAL, | | | GREASE TANK,SIZE,LOCATION AND CUT SHTS. | | | (4) REST RM'S (S-1) W/C P-1 NOT VENTED, | | | SHOW DWV PIPE SIZES FOR THIS BRANCH. | | | TRAP PRIMER WATER SUPPLY TO A PLUMBING | | | FIXTURE IN THE SAME ROOM.SEC 409.4 | | | (5)LOCATION AND SIZE OF WTR HTR,ENERGY | | | TYPE.SEC 104.2 | | | (6) THIS IS THE THIRD TIME IN FOR PLAN | | | REVIEW,PLEASE COMPLY WITH PREVIOUS | | | COMMENTS AND ABOVE COMMENTS,ATTACHED. | | | QUESTIONS CONTACT PAUL SCHMITZ | | | 561-659 8096 X 8233 | | | SEE ATTACHED GAS PIPING REQUIRMENTS. |
|