Plan Review Notes
Plan Review Notes For Permit 00090202
Permit Number 00090202
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEW RESUBMIT DENIED
 PLEASE ADDRESS PREVIOUS COMMENTS BY
 TIM LARGE DATED09-12-00
 (5)LOCATION & SIZE OF EX GREASE TRAP.
 CONTACT RODNEY COMPO 561-835-7423
 WPB.REG.SEWER PLANT FOR APPROVAL,WITH
 COPIES TO THIS OFFICE.
 (10) SPC SEC 914 DESIGN OF CIRCUIT/LOOP,
 W/C IN WOMENS LOUNGE, NOT VENTED,
 CONNECT STACK S-2 TO HORZ 3" W/C WASTE.
 (12) SUBMIT ISOMETRIC OF GREASE WASTE,
 ALL INDIRECT WASTE TO F/S.
 (13) GAS ISOMETRIC SEC 104.2 GAS PSI,
 TYPE OF MATERIAL,TOT. DEVELOPED LENGTH,
 TOT. BTU'S,LOCATION OF EMERGENCY SHUT
 OFF VALVE,W/MANUAL SHUT OFF UP STREAM,
 UNION DOWN STREAM, ALL BELOW CEILING.
 (16) HORIZONTAL WASTE & VENT SYSTEM,
 SEC 921.4.1,921.4.2 DESIGN 2 PIPE SIZES
 LARGER,MIN SIZE MAIN 4",BRANCHES3"
 HAND SINKS MAY BE 2".
 (17) ALL INDIRECT WASTE TO F/S
 (1) ADDED NOTE, DISHWASHER WASTE TO
 TO SANITARY SEWER,LOCAL ORDINANCE2425-90
 END OF COMMENTS PAUL SCHMITZ