| Plan Review Notes For Permit 00090202 |
| Permit Number |
00090202 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW RESUBMIT DENIED | | | PLEASE ADDRESS PREVIOUS COMMENTS BY | | | TIM LARGE DATED09-12-00 | | | (5)LOCATION & SIZE OF EX GREASE TRAP. | | | CONTACT RODNEY COMPO 561-835-7423 | | | WPB.REG.SEWER PLANT FOR APPROVAL,WITH | | | COPIES TO THIS OFFICE. | | | (10) SPC SEC 914 DESIGN OF CIRCUIT/LOOP, | | | W/C IN WOMENS LOUNGE, NOT VENTED, | | | CONNECT STACK S-2 TO HORZ 3" W/C WASTE. | | | (12) SUBMIT ISOMETRIC OF GREASE WASTE, | | | ALL INDIRECT WASTE TO F/S. | | | (13) GAS ISOMETRIC SEC 104.2 GAS PSI, | | | TYPE OF MATERIAL,TOT. DEVELOPED LENGTH, | | | TOT. BTU'S,LOCATION OF EMERGENCY SHUT | | | OFF VALVE,W/MANUAL SHUT OFF UP STREAM, | | | UNION DOWN STREAM, ALL BELOW CEILING. | | | (16) HORIZONTAL WASTE & VENT SYSTEM, | | | SEC 921.4.1,921.4.2 DESIGN 2 PIPE SIZES | | | LARGER,MIN SIZE MAIN 4",BRANCHES3" | | | HAND SINKS MAY BE 2". | | | (17) ALL INDIRECT WASTE TO F/S | | | (1) ADDED NOTE, DISHWASHER WASTE TO | | | TO SANITARY SEWER,LOCAL ORDINANCE2425-90 | | | END OF COMMENTS PAUL SCHMITZ |
|