Text |
| 2001-01-08 00:00:00 | 1)INDICATE OCCUPANT LOAD OF RESTAURANT |
| | BASED ON SPC TABLE 407.SEE SPC SEC. |
| | 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS. |
| | |
| | 2)SUBMIT DAY,MONTH AND YEAR BUILDING WAS |
| | PERMITTED FOR CONSTRUCTION.COMPLIANCE |
| | W/FLA.STATUTE 553.141 MAY BE REQD. |
| | |
| | 3)SUBMIT OCCUPANT LOAD OF BANQUET ROOM |
| | FOR POSSIBLE COMPLIANCE W/F.S.553.141. |
| | |
| | 4)PLANS SHALL BE ROUTED TO DEPT.OF BUS. |
| | REGULATION FOR REVIEW AND APPROVAL PRIOR |
| | TO REVIEW BY THIS DEPT.COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.101.4.7. |
| | |
| | 5)SUBMIT VERIFICATION OF EXISTING GREASE |
| | INTERCEPTOR.NOTE SIZE AND LOCATION ON |
| | PLAN.CONTACT R.COMPO AT 561-835-7423 FOR |
| | APPROVAL.SUBMIT COPY OF APPROVAL TO THIS |
| | OFFICE.SPC SEC.101.4.7. |
| | |
| | 6)PER SPC TABLE 407-THE MINIMUM NUMBER |
| | OF REQUIRED SANITARY FACILITIES IS AS |
| | FOLLOWS:MALES-4 WATER CLOSETS |
| | 2 LAVATORIES |
| | FEMALES -4 WATER CLOSETS |
| | 2 LAVATORIES |
| | THIS DOESN'T INCLUDE COMPLIANCE W/F.S. |
| | 553.141. |
| | |
| | 7)SHT.A2.4-"TYP.MOUNTING HEIGHT"-REVISE |
| | GRAB BAR MEASUREMENTS.(LENGTH AND MOUNT- |
| | ING HEIGHTS)THEY DO NOT COMPLY W/FACBC. |
| | AND DIMENSIONS SHALL BE LEGIBLE. |
| | |
| | 8)SHT.A2.4-CENTERLINE OF ACCESSIBLE |
| | WATER CLOSET FROM WALL SHALL COMPLY W/ |
| | FACBC SEC.4.16 AND FIG.#30. |
| | |
| | 9)SHT.A2.4-IDENTIFY ACCESSIBLE URINAL |
| | ON PLANS AND SHOW CLEAR FLOOR SPACE FOR |
| | URINAL.FACBC SEC.4.18. |
| | |
| | 10)DESIGN OF PLUMBING SYSTEM SHALL |
| | COMPLY W/SPC SEC.914 FOR CIRCUIT AND |
| | LOOP SYSTEM IF THAT IS THE INTENT. |
| | |
| | 11)SHT.P-1-LAYOUT OF PLUMBING SYSTEM |
| | ON FLOOR PLAN DOESN'T CORRELATE W/ |
| | SANITARY RISER ON P-2.COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.104.2.1. |
| | |
| | 12)SUBMIT AN ISOMETRIC DRAWING FOR ALL |
| | NEW PLUMBING WORK TO BE INSTALLED.COUNTY |
| | WIDE AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | 13)SUBMIT A GAS ISOMETRIC FOR ANY NEW |
| | GAS WORK.SHOW DISTANCE FROM POINT OF |
| | DELIVERY TO MOST REMOTE OUTLET,TYPE OF |
| | PIPING,TYPE OF GAS,DELIVERY PSI ETC.IN |
| | ORDER TO VERIFY EXISTING SYSTEM COMPLIES |
| | W/CODE.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 101.3.1 |
| | |
| | 14)DRY VENTS NOT PERMITTED.BASE OF STACK |
| | SHALL BE WASHED.SPC SEC.906.2.1. |
| | |
| | 15)SHOW SIZE OF EXIST.STACK S/1.COUNTY- |
| | WIDE AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | 16)HORIZ.COMBINATION WASTE AND VENT |
| | SYSTEM SHALL COMPLY W/SPC SEC.921. |
| | |
| | 17)ALL INDIRECT WASTES SHALL DISCHARGE |
| | TO FLOOR SINKS,NOT FLOOR DRAINS.SPC SEC. |
| | 804.1,807.1.3. |
| | |
| | 18)SIZE OF PIPE INSULATION SHALL COMPLY |
| | W/F.E.C.TABLE 411. |
| | |
| | 19)SIZE EXISTING RISER S/1 AND VENT |
| | STACK.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 104.2.1. |
| | |
| | 20)ALL SHEETS SHALL BE SIGNED AND SEALED |
| | PER F.A.C.61G15-23.002.(SEE P-1). |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |