Plan Review Notes
Plan Review Notes For Permit 00090202
Permit Number 00090202
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)INDICATE OCCUPANT LOAD OF RESTAURANT
 BASED ON SPC TABLE 407.SEE SPC SEC.
 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS.
  
 2)SUBMIT DAY,MONTH AND YEAR BUILDING WAS
 PERMITTED FOR CONSTRUCTION.COMPLIANCE
 W/FLA.STATUTE 553.141 MAY BE REQD.
  
 3)SUBMIT OCCUPANT LOAD OF BANQUET ROOM
 FOR POSSIBLE COMPLIANCE W/F.S.553.141.
  
 4)PLANS SHALL BE ROUTED TO DEPT.OF BUS.
 REGULATION FOR REVIEW AND APPROVAL PRIOR
 TO REVIEW BY THIS DEPT.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.101.4.7.
  
 5)SUBMIT VERIFICATION OF EXISTING GREASE
 INTERCEPTOR.NOTE SIZE AND LOCATION ON
 PLAN.CONTACT R.COMPO AT 561-835-7423 FOR
 APPROVAL.SUBMIT COPY OF APPROVAL TO THIS
 OFFICE.SPC SEC.101.4.7.
  
 6)PER SPC TABLE 407-THE MINIMUM NUMBER
 OF REQUIRED SANITARY FACILITIES IS AS
 FOLLOWS:MALES-4 WATER CLOSETS
 2 LAVATORIES
 FEMALES -4 WATER CLOSETS
 2 LAVATORIES
 THIS DOESN'T INCLUDE COMPLIANCE W/F.S.
 553.141.
  
 7)SHT.A2.4-"TYP.MOUNTING HEIGHT"-REVISE
 GRAB BAR MEASUREMENTS.(LENGTH AND MOUNT-
 ING HEIGHTS)THEY DO NOT COMPLY W/FACBC.
 AND DIMENSIONS SHALL BE LEGIBLE.
  
 8)SHT.A2.4-CENTERLINE OF ACCESSIBLE
 WATER CLOSET FROM WALL SHALL COMPLY W/
 FACBC SEC.4.16 AND FIG.#30.
  
 9)SHT.A2.4-IDENTIFY ACCESSIBLE URINAL
 ON PLANS AND SHOW CLEAR FLOOR SPACE FOR
 URINAL.FACBC SEC.4.18.
  
 10)DESIGN OF PLUMBING SYSTEM SHALL
 COMPLY W/SPC SEC.914 FOR CIRCUIT AND
 LOOP SYSTEM IF THAT IS THE INTENT.
  
 11)SHT.P-1-LAYOUT OF PLUMBING SYSTEM
 ON FLOOR PLAN DOESN'T CORRELATE W/
 SANITARY RISER ON P-2.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 12)SUBMIT AN ISOMETRIC DRAWING FOR ALL
 NEW PLUMBING WORK TO BE INSTALLED.COUNTY
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 13)SUBMIT A GAS ISOMETRIC FOR ANY NEW
 GAS WORK.SHOW DISTANCE FROM POINT OF
 DELIVERY TO MOST REMOTE OUTLET,TYPE OF
 PIPING,TYPE OF GAS,DELIVERY PSI ETC.IN
 ORDER TO VERIFY EXISTING SYSTEM COMPLIES
 W/CODE.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.3.1
  
 14)DRY VENTS NOT PERMITTED.BASE OF STACK
 SHALL BE WASHED.SPC SEC.906.2.1.
  
 15)SHOW SIZE OF EXIST.STACK S/1.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 16)HORIZ.COMBINATION WASTE AND VENT
 SYSTEM SHALL COMPLY W/SPC SEC.921.
  
 17)ALL INDIRECT WASTES SHALL DISCHARGE
 TO FLOOR SINKS,NOT FLOOR DRAINS.SPC SEC.
 804.1,807.1.3.
  
 18)SIZE OF PIPE INSULATION SHALL COMPLY
 W/F.E.C.TABLE 411.
  
 19)SIZE EXISTING RISER S/1 AND VENT
 STACK.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 20)ALL SHEETS SHALL BE SIGNED AND SEALED
 PER F.A.C.61G15-23.002.(SEE P-1).
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.