| Plan Review Notes For Permit 00090202 |
| Permit Number |
00090202 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* UNSAT ******************** | | | | | | 1)NOTE: PLEASE COMPLETE AND SHOW LOAD | | | CALCULATIONS. LOADS SHOWN AS ??? THIS IS | | | NOT ACCEPTABLE. ALL LOADS MUST BE SHOWN | | | 215-5. PER ART;220 OF THE NEC. | | | | | | 2)NOTE: PLEASE SHOW NEW PANEL "SP" ON | | | PANEL SCHEDULE. NOT AS SUB PANEL?? | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCS AND WHAT | | | DERATING FACTORS YOU ARE USING. | | | PLEASE NOTE ALL CONTINUOUS LOADS ARE TO | | | BE SHOWN AT 125%. (LIGHTING, HEAT LAMPS | | | ETC) | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|