Plan Review Notes
Plan Review Notes For Permit 00090202
Permit Number 00090202
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************* UNSAT ********************
  
 1)NOTE: PLEASE COMPLETE AND SHOW LOAD
 CALCULATIONS. LOADS SHOWN AS ??? THIS IS
 NOT ACCEPTABLE. ALL LOADS MUST BE SHOWN
 215-5. PER ART;220 OF THE NEC.
  
 2)NOTE: PLEASE SHOW NEW PANEL "SP" ON
 PANEL SCHEDULE. NOT AS SUB PANEL??
  
 3)NOTE: PLEASE SHOW LOAD CALCS AND WHAT
 DERATING FACTORS YOU ARE USING.
 PLEASE NOTE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%. (LIGHTING, HEAT LAMPS
 ETC)
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  