| Plan Review Notes For Permit 00090138 |
| Permit Number |
00090138 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)THE SANITARY RISERS DO NOT CORRELATE | | | W/THE APPROPRIATE FLOOR PLANS.(APPEAR TO | | | BE FLIPPED.)COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | 2)OPTIONAL LAUNDRY TRAY ON FLOOR PLAN | | | NOT SHOWN ON SANITARY RISER.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 3)PLANS SHOW 50 GAL.WATER HEATERS AND | | | ENERGY CALCS.NOTE 40 GAL.COMPLY W/F.E.C. | | | SEC.103.2. | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. | | | | | | *****NOTE:THESE COMMENTS ALSO APPLY TO | | | PERMIT NUMBERS:00090140 | | | 00090143 | | | 00090145 | | | 00090147 | | | 00090148 |
|