| Date |
Text |
| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-STRUCTURAL DRAWINGS NEED TO BE SIGNED, |
| | SEALED AND DATED BY THE STRUCTURAL |
| | ENGINEER OF RECORD. |
| | -STRUCTURAL DRAWINGS TO BE COORDINATED |
| | WITH THE ARCHITECTURAL DRAWINGS. |
| | KEYED DETAILS DON'T MATCH THE ACTUAL |
| | CONDITIONS. PLEASE REVIEW ALL ARCH'AL |
| | AND STRUCTURAL DRAWINGS AND PROVIDE |
| | A CLEAR COMPLETE SET OF CONSTRUCTION |
| | DOCUMENTS. |
| | 2-REVISE THE DESIGN CERTIFICATION FOR |
| | WIND LOAD COMPLIANCE FORM. MEAN ROOF |
| | HEIGHT IS +/- 31'-6" NOT 24'. SEE |
| | COMMENTS ON THE FORM. |
| | -ALSO, CLARIFY WHAT IS THE EB6612 |
| | NUMBER FOR. THIS DOESN'T MATCH THE |
| | ENGINEER LICENSE NUMBER ON THE SEAL. |
| | 3-THERE IS NO INFORMATION GIVEN FOR THE |
| | SPIRAL STAIRS. SPECIFICATIONS,FOOTING, |
| | DIMENSIONS, DETAILS, ETC. |
| | 4-PROVIDE CONSTRUCTION DETAILS FOR BAY |
| | WINDOW AT BREAKFAST AREA. ATTACHMENT |
| | OF WINDOWS TO THE STEEL COLUMN. |
| | 5-PROVIDE ENGINEERS CERTIFICATION FOR |
| | SOIL DEMUCKING AND FILLING AS PER |
| | SOIL TEST REPORT RECOMMENDATIONS. |
| | 6-PROVIDE CALCULATIONS FOR VENTILATION |
| | OF ATTIC. SEC 2309.7 SBC 1997. VERIFY |
| | SIZE AND SPACING OF VENTS SPECIFIED. |
| | 7-OWNER/AGENT TO SIGN AND DATE THE |
| | ENERGY CALCULATIONS. |
| | 8-PROVIDE ATTIC ACCESS AT MASTER BEDROOM |
| | ROOF WING. SEC 2309.6 SBC 1997. |
| | 9-GARAGE DOORS PRODUCT APPROVAL DON'T |
| | MEET THE DESIGN PRESSURES CALCULATED |
| | BY THE STRUCTURAL ENGINEER. |
| | 10-SPECIFY AND IDENTIFY THE SHEARWALLS. |
| | 11-PROVIDE PRODUCT APPROVAL FOR: |
| | -FRENCH DOORS WITH FIXED GLASS ASSEMBLY |
| | AS SHOWN ON COVERED PATIO AREA. |
| | -FLAT ROOF SYSTEM (EXPIRED). |
| | -SINGLE HUNG WINDOWS AND ROUND WINDOWS. |
| | -MULLIONS FOR MISSILE IMPACT ASSEMBLIES |
| | -FIREPLACE UL LISTING & SPECIFICATIONS. |
| | 12-PROVIDE COMPLETE INFORMATION FOR |
| | STORM PANELS, INCLUDING COMPLETE |
| | INSTALLATION SCHEDULE (SEE ATTACHED |
| | SAMPLE) AND KEY PLAN AND CIRCLE THE |
| | MOUNTING CONDITIONS AND ANCHORS USED. |
| | NOTE:THIS INFORMATION MAY BE SUBMITTED |
| | LATER UNDER A SEPARATE PERMIT. |
| | 13-NORANDEX WINDOWS AND DOORS SITE |
| | SPECIFIC PRODUCT APPROVAL NEED TO BE |
| | SIGNED,SEALED,DATED BY THE STRUCTURAL |
| | ENGINEER OF RECORD AS WELL. |
| | -SPECIFY WINDOWS/DOORS AND COMPONENTS |
| | TO BE USED IN THIS SITE SPECIFIC |
| | APPLICATION. |
| | -ENGINEER TO INCLUDE LEGIBLE NAME, |
| | ADDRESS, LICENSE NUMBER AS REQUESTED |
| | BY CHAPTER 471 OF FLORIDA STATUTES. |
| | 14-SEE COMMENTS ON PRODUCT APPROVALS |
| | SUBMITTED AND ON REVIEWED SET OF |
| | DRAWINGS. |
| | |
| | |
| | |