| Plan Review Notes For Permit 00090113 |
| Permit Number |
00090113 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: AS PER 215-5 AND 110-9 AND AS | | | ASKED FOR ON FIRST REVIEW, AIC RATINGS | | | FOR ALL EQUIPMENT IS REQ`D ON PLANS FOR | | | MAIN DISCONNECTS AND PANELS. ALL MUST BE | | | RATED PER 110-9. THE AVAILABLE FAULT | | | CURRENT CAN BE GOTTEN FROM FPL AND THE | | | EQUIPMENT CAN BE PER THEIR A.F.C OR A | | | FAULT CURRENT CALCUALTION CAN BE DONE TO | | | SEE IF EQUIPMENT WITH LOWER AIC RATINGS | | | CAN BE INSTALLED. IF THERE ARE ANY | | | QUESTIONS ON THE ABOVE, PLEASE DO NOT | | | HESITATE IN CONTACTING ME. | | | | | | 2)NOTE: ALSO PLEASE CLARIFY THE LOADS | | | SHOWN FOR A/C`S?? PANELS LIST LOADS AT | | | 5KW OR 10KW AND THEN IN THE FAR RIGHT | | | COLULMN LOADS ARE LISTED WITH AN ADDIT- | | | -IONAL 700W ?? PLEASE EXPLAIN. | | | | | | | | | PLEASE SUBMIT THE ABOVE. THE AIC RATINGS | | | FOR EQUIPMENT IS REQ`D AND IF THERE | | | ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|