Plan Review Notes
Plan Review Notes For Permit 00090113
Permit Number 00090113
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 PLEASE SEE E-1 FOR THE FOLLOWING.
  
 1)NOTE: PLEASE INCLUDE BLDG STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 PER 250-50
  
 2)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL EQUIPMENT BEING INSTALLED. MAINS/
 PANELS/BREAKERS ALL MUST BE RATED FOR
 AVAILBLE FAULT CURRENT PER 110-9.215-5
  
 3)NOTE: PLEASE SEE LOADS SHOWN ON LOAD
 CALCULATIONS,, THE LOADS SHOWN DO NOT
 ADD UP TO WHAT IS SHOWN FOR TOTAL LOAD.
 ADDING THE KVA SHOWN PUTS SERVICE OVER
 300AMPS.PLEASE CLARIFY AND INCREASE
 SERVICE IF NEEDED. PER 220
  
 4)NOTE: PLEASE SHOW SIZE OF METERCAN.
 215-5
  
 5)NOTE: PLEASE SHOW ALL CONDUCTOR SIZES
 ON RISER DIAGRAM.(GUTTER/METER) ETC.
  
 6)NOTE: PLEASE SEE 250-122 FOR REQ`D
 EQUIPMENT GROUNDING CONDUCTOR AFTER
 FIRST MEANS OF DISCONNECT.
  
 7)NOTE: PLEASE SEE CONDUITS SHOWN AS 3/4
 INCH CONDUIT W/ 3# 3`S??? CONDUIT FILL
 PER APPENDIX "C" OF THE NEC.
 PLEASE CORRECT.
  
 8)NOTE: PLEASE CORRELATE LOADS FOR A/C
 UNITS ON PANEL SCHEDULES.ONE SHOWS LOAD
 AT 5KW AND THEN 5.7KW?? AND SO ON FOR
 A/C LOADS??
 PLEASE CLARIFY.
  
 PLEASE SEE E-2 FOR THE FOLLOWING.
  
 1)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AND
 ADAPTABLE SLLEPING ROOMS WHICH ARE ROOMS
 W/ CLOSETS AND OR BATHROOMS. ALSO
 SMOKE DETECTOR ARE REQ`D ON EACH LEVEL
 OF A MULTI-LEVEL RESIDENCE AND IN COMMON
 AREA.PLEASE SEE NFPA-72 2-2.1.1.1
 ALSO SBCCI 97 FOR NFPA 101
  
 PLEASE SEE E-3 FOR THE FOLLOWING.
  
 1)NOTE: PLEASE NOTE SMOKE DETECTOR REQ`
 -MENTS IN THIS AREA ALSO.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW, IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372