| 2001-11-13 00:00:00 | ******************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE NOTE THAT THE PLANS |
| | SUBMITTED FOR GUEST/GARAGE DO NOT |
| | CORRELATE WITH PLANS FORMAIN HOUSE |
| | SERVICE. TWO PLANS /TWO SERVICES? |
| | |
| | 2)NOTE: PLEASE CLARFIY SIZE OF METERCAN, |
| | SHOWN AS EXISTING? LOAD SHOWN AT 269.9A |
| | |
| | 3)NOTE: PLEASE NOTE THAT ON GUEST HOUSE |
| | METER AND TWO DISCONNECTS ARE SHOWN, BUT |
| | DOES NOT SHOW WHERE PANEL IS ON PLANS? |
| | NOTE NEXT TO SERVICE SAYS, "GUEST HOUSE |
| | PANEL" , THEN WHERE IS MAIN DISCONNECT |
| | SHOWN ON RISER DIAGRAM? |
| | |
| | 4)NOTE: PLEASE NOTE MISSING GROUNDING |
| | AT DETACHED MAIN HOUSE. 250-32. |
| | |
| | 5)NOTE: PLEASE INDICATE MCB FOR PANEL |
| | AT MAIN HOUSE DETACHED FROM GUEST HOUSE |
| | SERVICE. 225-31 |
| | |
| | 6)NOTE: PLEASE NOTE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS BETWEEN MAIN DISC`S |
| | AND PANELS. 250-122 |
| | |
| | 7)NOTE: PLEASE CLARIFY 2/0`S SHOWN FOR |
| | 100A EQUIPMENT? |
| | |
| | 8) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | ARE THE GFI CIRCUITS THAT ARE SHOWN ON |
| | PANEL SCHEDULE FOR THIS? |
| | |
| | 9)NOTE: PLEASE SHOW GARAGE ON THE |
| | ELECTRICAL PLAN AND SHOW REQ`D ELEC. |
| | FOR GARAGE. PLAN SHOW GARAGE AS DETACHED |
| | ?? PLEASE CLARIFY. |
| | |
| | PLEASE MAKE THE ABOVE CORRECTIONS AND |
| | SUBMIT THE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |