| 2001-11-16 00:00:00 | REVISION DENIED |
| | |
| | 1) PROVIDE AN EMERGENCY ESCAPE AND |
| | RESCUE OPENING FOR THE SECOND FLOOR |
| | GUEST ROOM PER 97 SBC SEC. 1005.4.1. |
| | THE WINDOW MUST HAVE A MINIMUM NET CLEAR |
| | OPENING OF 5.7 SQ.FT. WITH A MINIMUM NET |
| | CLEAR OPENING HEIGHT OF 24" AND MINIMUM |
| | NET CLEAR OPENING WIDTH OF 20". THE SILL |
| | HEIGHT CAN NOT BE MORE THAN 44" PER 97 |
| | SBC SEC.1005.4.4 AND 1005.4.3. |
| | |
| | 2)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - STRUCTURAL WINDOW MULLIONS |
| | - STORM PANELS OR IMPACT GLASS |
| | |
| | 3) PROVIDE ACCESS TO ATTIC SPACE PER |
| | 97 SBC SEC. 2309.6. |
| | |
| | 4) EXTERIOR EXITWAY STAIRS: |
| | EXTERIOR STAIRS SHALL BE SEPARATED FROM |
| | THE INTERIOR OF THE BUILDING BY WALLS |
| | WITH A FIRE RESISTANCE RATING OF NOT |
| | LESS THAN 1 HOUR, WITH FIXED OR SELF- |
| | CLOSING OPENING PROTECTIVES AS REQUIRED |
| | FOR ENCLOSED STAIRS. PROTECTION SHALL |
| | EXTEND VERTICALLY FROM THE GROUND TO A |
| | POINT 10 FEET ABOVE THE TOPMOST LANDING |
| | OR THE ROOF LINE WHICHEVER IS LOWER AND |
| | HORIZONTALLY 10 FEET FROM EACH SIDE OF |
| | THE STAIRWAY. OPENINGS WITHIN THE 10 |
| | FOOT HORIZONTAL EXTENSION OF THE |
| | PROTECTED WALLS BEYOND THE STAIRWAY |
| | SHALL BE EQUIPPED WITH FIXED 3/4- HOUR |
| | ASSEMBLIES. 97 SBC SEC. 1006.2.4 THE NEW |
| | DOORS AND WINDOWS IN THIS AREA MUST |
| | COMPLY. SEE 97 SBC SEC. 705.1.3 FOR |
| | APPROVED TYPES OF FIRE WINDOWS AND DOORS |
| | |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |