| 2001-01-08 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE CLARIFY PLANS, YOU SHOW |
| | GARAGE AS FUTURE BUT ARE SHOWING AS NEW |
| | ROOF ETC??? ELECTRIC REQ`D IF NEW? |
| | |
| | 2)NOTE: PLEASE SHOW NEW CU FOR A/C |
| | DISCONNECT PER 440-11 AND WP GFI. |
| | |
| | 3)NOTE: PLEASE NOTE PER FIRST REVIEW, |
| | MISSING GFI FOR REAR OF BLDG. 210-52E |
| | |
| | 4)NOTE: PLEASE SHOW WINDOW A/C BEING TAK |
| | -EN OUT? IS A/C ON FIRST FLOOR FEEDING |
| | SECONG FLOOR? |
| | |
| | 5)NOTE: LOAD CALCULATIONS (SQ FT) DOES- |
| | -NOT MATCHFLOOR SQ FT.?? IS FIRST |
| | FLOOR AND SECOND FLOOR ON SAME PANEL? |
| | |
| | 6)NOTE: SINCE FIRST REVIEW A NEW SERVICE |
| | IS BEING SHOWN.. 100AMP PANEL W/ 2/0 |
| | WIRE? IS THIS CORRECT? |
| | PLEASE SUBMIT AIC RATING OF NEW MAIN |
| | DISCONNECT AND PANEL. MUST BE RATED FOR |
| | AVAILABLE FAULT CURRENT PER 110-9 AND |
| | 215-5. |
| | |
| | 7)NOTE: PLEASE SHOW BATH(S) CIRCUIT(S) |
| | REQ`D PER 210-11-C-3 AND 210-52D. #12 AN |
| | 20AMP. |
| | |
| | 8)NOTE: PLEASE NOTE;YOU SHOW DISCONNECTS |
| | ON AHU AND WATER HEATER? NOTE 110-26 FOR |
| | DISC CLEARENCE. PANEL IS WITHIN SIGHT |
| | ACCROSS HALL?S |
| | |
| | 9)NOTE: PLEASE CHECK LOAD SHOWN FOR |
| | WATER HEATER ON #12 AND 20AMP BRKR? |
| | PLEASE NOTE THAT OCP FOR A 4500W WATER |
| | HEATER MUST BE 125%. 4500W EXCEEDS 80% |
| | OF BRKR. |
| | |
| | 10)NOTE: PLEASE SEE 250-122 AND SIZE |
| | EQUIPMENT GROUNDING CONDUCTOR FROM |
| | MAIN TO PANEL. |
| | |
| | 1)NOTE: PLEASE SHOW EGRESS LIGHTING FOR |
| | MAIN GUEST ROOM FIRST FLOOR. PER 210-70 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-659-8096 EXT 8372 |