| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT PANEL SCHEDULE | | | AND LOAD CALCULATIONS FOR NEW REMODELED | | | AREA.215-5 | | | THERE APPEARS TO BE TWO SEPARATE APART- | | | -MENTS? HOW ARE THEY BEING FED? IS THERE | | | SEPARATE PANELS FOR EACH FLOOR? | | | PLEASE SHOW CLARIFICATION.MEANS OF DISC? | | | | | | 2)NOTE: ALSO MORE THAN 50% OF THIS STRUC | | | -TURE IS BEING REMODELED.? | | | PLEASE INSTALL SMOKE DETECTOR ON 2ND | | | FLOOR.WIRE INLINE | | | | | | 3)NOTE: PLEASE ADD GFI OUTLETS PER 210- | | | -52-E. | | | | | | 4)NOTE: PLEASE SEE 210-52D AND 210-11-C- | | | -3 FOR REQ`D BATH(S) CIRCUIT(S). MUST BE | | | #12 AND 20AMP. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|