| Plan Review Notes For Permit 00090102 |
| Permit Number |
00090102 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | OUTSIDE AIR PER ASHRAE 62-89 REQUIRED | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR TO | | | BE TIED TO HORN AND STROBE FOR NOTIFICA- | | | TION PER NFPA 90A 4-4.4 |
|