Plan Review Notes
Plan Review Notes For Permit 00090081
Permit Number 00090081
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************DENIED******************
  
 1)STRUCTURE IS LOCATED IN FLOOD ZONE"AO"
 PLEASE PROVIDE ELEVATION CERTIFICATE
 AFTER PROJECT IS COMPLETED PER NEW FEMA
 REQUIREMENTS.
  
 2)PROVIDE SOIL REPORT SIGNED,SEALED AND
 DATED (WET SIGNATURE). FL STATUTES
 REQUIRE DOCUMENTS SUBMITTED FOR PUBLIC
 RECORD BY ARCHITECTS AND ENGINEERS TO
 SIGN,SEALED AND DATED.
  
 3)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND RECEIPT
 SUBMITTED TO CITY OF WPB CONSTRUCTION
 SERVICES DEPT. BEFORE A PERMIT TO
 CONSTRUCT WILL BE ISSUED.
  
 4)ARCHITECT IS REQUIRED TO DATE EACH
 DRAWING AS WELL AS SIGN AND SEAL THEM
 PER FL STATUTES 481.221(A). PLEASE HAVE
 ARCHITECT DATE PLANS.
  
 5)PROVIDE ENGINEERED CALCULATIONS OR
 LETTER FROM MANUFACTURER CERTIFYING THE
 APPLICATION OF JOIST HANGER EHUH 210 ON
 MASONRY AND TYPE,SIZE AND NUMBER OF
 FASTENERS REQUIRED.
  
 6)PLEASE INDICATE LOCATION OF EHUH 210
 CONNECTORS ON TRUSS FRAMING DRAWING
 SHEET 7.
  
 7)GIRDER TRUSS TO CONC. COL.DETAIL IS
 NOT PROPERLY IDENTIFIED ON PLANS.PLEASE
 CLARIFY.
  
 8)ANCHOR LEGEND ON SHEET 8 ITEM #2 LISTS
 CAPACITY OF EACH STRAP AS 2800 LBS.
 PLEASE CORRECT.
  
 9)DETAIL #6 ON SHEET 8 IS CROSSED OUT,
 ON SHEET 7 IT IS SHOWN. PLEASE CLARIFY.
  
 10)SECTION 1/A2 ON SHEET 2 DRAWING IS
 OF EXTERIOR GARAGE WALLS AND DETAIL 1/A2
 SHOWS SECTION THRU SHOWER CURB. PLEASE
 CLARIFY.
  
 11)DETAIL 1/2 SECTION THRU GARAGE CURB
 WITH (2) 9" BLOCKS IS NOT IDENTIFIED ON
 DRAWING ON SHEET 2. PLEASE CLARIFY.
  
 12)PLEASE PROVIDE ADDITIONAL DATA ON
 2 HR FIRE RATED BLOCK THAT WILL BE USED
 ON THIS PROJECT. FIRE TEST DATA ON
 SPECFIC PRODUCT THAT IS TO BE USED IS
 REQUIRED.