| Notes |
| Date |
Text |
| 2001-01-26 00:00:00 | TRUSSES | | | | | | TRUSS SUBMITTAL DENIED. | | | | | | TRUSS S3 ON THE TRUSS ENGINEERING LAYOUT | | | IS NOT INDICATED ON THE ARCHITECTURAL | | | DRAWINGS. IT HAS THREE BEARING POINTS. | | | NO ANCHOR HAS BEEN SPECIFIED FOR THE | | | INTERIOR BEARING POINT, WHICH HAS AN | | | INDICATED UPLIFT OF 1907#. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|