| Plan Review Notes For Permit 00090066 |
| Permit Number |
00090066 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-26 00:00:00 | TRUSSES | | | | | | TRUSS SUBMITTALS DENIED. | | | | | | - THE FOLLOWING TRUSSES HAVE UPLIFT | | | VALUES GIVEN ON THE TRUSS DRAWINGS | | | WHICH EXCEED THE CAPACITY OF THE ANCHORS | | | INDICATED ON THE ARCHITECTURAL DRAWINGS: | | | T8U= 1538# | | | T9U= 1538# | | | T8A U= 1594# | | | T9A U= 1594# | | | T10 U= 1950# | | | T11 U= 1915# | | | | | | PLEASE HAVE DESIGNER OF RECORD REVIEW | | | AND MAKE ANY NECESSARY CORRECTIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|