3 |
|
| Notes |
| Date |
Text |
| 2001-11-05 00:00:00 | *******************DENIED*************** | | | | | | | | | PLAN SHEETS M2.00, M2.01 & M2.03 | | | INDICATE HEAT WHEEL ON ROOF.PLAN | | | SHEET M2.03 DOES NOT SHOW A DETAIL OF | | | THE HEAT WHEEL AS THE ORIGINAL | | | SUBMITTAL DID. | | | | | | PROVISO ON THE ORIGINAL PLAN WAS NOT | | | ADDRESSED.MINIMUM OF 10' SEPARATION | | | BETWEEN O.A. AND EXHAUST. | | | | | | PLEASE PROVIDE DETAIL OF HEAT WHEEL | | | WITH SEQUENCE OF OPERATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|