| Plan Review Notes For Permit 00090054 |
| Permit Number |
00090054 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | 1. PROVIDE BETTER QUALITY DRAWING WITH | | | DETAILED INFORMATION ON CFM @ DROPS | | | AND ALL DUCT SIZES | | | 2.DUCT R-VALUE TO BE SHOWN | | | 3. CONDENSING UNITS ON ROOF TO BE MOUNT- | | | ED ON STANDS WITH MINIMUM CLEARANCE OF | | | 18" BETWEEN ROOF SURFACE AND BOTTOM OF | | | SUPPORT STRUCTURE OF STAND AND MEETING | | | WIND LOAD RATINGS. PROVIDE ENGINEERED | | | INFORMATION ON STAND. | | | 4. IS DUCT LOCATED IN ATTIC OR IN SOFFIT | | | BELOW CEILING? P[ROVIDE INFORMATION. | | | 5 PROVIDE CONDENSATE DRAINLINE LOCATION | | | INFORMATION. |
|