| Plan Review Notes For Permit 00081735 |
| Permit Number |
00081735 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SUBMIT COPY OF APPROPRIATE GAS SIZING | | | TABLE FROM S.G.C.,NFPA-54,OR MANUF.OF | | | PIPE MATERIAL. | | | | | | 2)SUBMIT CALCULATIONS FOR COMBUSTION AIR | | | COMPLY W/SGC 402.4.4.3,402.4.4.4.SIGNED | | | AND SEALED BY DESIGN PROFESSIONAL. | | | | | | 3)SUBMIT PERMIT APPLICATION SIGNED BY | | | CONTRACTOR AND NOTARIZED. | | | | | | 4)SUBMIT TWO COMPLETE SETS OF PLANS FOR | | | REVIEW.(COMPILE ALL SHEETS.) | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER |
|